INSTRUCTION MANUAL [PDF]

ers" (BLRBAC August, 1982 and revisions April, 1991, and March, 2001). 2.1. DIGITAL DIVERT CONTROL SYSTEM DD-01. Figure

0 downloads 4 Views 3MB Size

Recommend Stories


Download Instruction Manual PDF
Respond to every call that excites your spirit. Rumi

Instruction Manual (PDF)
Where there is ruin, there is hope for a treasure. Rumi

PDF - Instruction Manual W4327D
The butterfly counts not months but moments, and has time enough. Rabindranath Tagore

instruction manual instruction manual
Don't ruin a good today by thinking about a bad yesterday. Let it go. Anonymous

Thule KIT3042 PDF Instruction Manual
At the end of your life, you will never regret not having passed one more test, not winning one more

instruction manual instruction manual nstruction manual
The butterfly counts not months but moments, and has time enough. Rabindranath Tagore

Instruction Manual
I tried to make sense of the Four Books, until love arrived, and it all became a single syllable. Yunus

instruction manual
Be who you needed when you were younger. Anonymous

Instruction Manual
Stop acting so small. You are the universe in ecstatic motion. Rumi

instruction manual
Pretending to not be afraid is as good as actually not being afraid. David Letterman

Idea Transcript


INSTRUCTION MANUAL FOR DD-01 DIGITAL DIVERT CONTROL SYSTEM VERSION 4.1. WITH MAIN PROGRAM 8.5 OR HIGHER

WARNING The process medium may be hot or otherwise hazardous. Precautions when removing the sensor from the process line: Make sure that the process line is not under pressure. Open a vent valve to the atmosphere. For a retractor/isolation valve the line pressure should be within specifications. For a prism wash system, close a hand valve for the wash medium and disable the wash valve. Loosen the clamp or flange bolts cautiously, be prepared to tighten again. Be out of the way of any possible splash and ensure the possibility of escape. Use shields and protective clothing adequate for the process medium. Do not rely on avoidance of contact with the process medium. After removal of the sensor, it may be necessary to mount a blind flange for security reasons.

Document/Revision No. IMD 1/5

Effective: June 20, 2005

This product manual is delivered to the end-user with a K-Patents product. Information in this manual is subject to change without notice. The latest manual version is freely available at http//www.kpatents.com/. You can also contact [email protected]. THE PASSWORD FOR PR-01-S IS 7 8 4 5 1 2 IN PROGRAM VERSIONS 4.0 AND HIGHER.

K-PATENTS OY

K-PATENTS OY

K-PATENTS,INC.

Postal address: P.O. Box 77 FIN-01511 Vantaa, Finland

Street address: Elannontie 5 FIN-01510 Vantaa, Finland

1804 Centre Point Circle, Suite 106, Naperville, IL 60563

Tel. + 358-9-825 6640 Fax +358-9-825 66461 E-mail: [email protected] http://www.kpatents.com/

Tel. + 358-9-825 6640 Fax +358-9-825 66461

Tel. 630-955 1545 Fax 630-955 1585 E-mail: [email protected] http://www.kpatents.com/

1

1. TABLE OF CONTENTS

1

TABLE OF CONTENTS........................................................................................................................1

2

GENERAL INFORMATION .................................................................................................................2 2.1 Digital divert control system DD-01 .................................................................................................2 2.2 Operator panel...................................................................................................................................3 2.3 Alarms ...............................................................................................................................................4 2.4 Prism wash ........................................................................................................................................4 2.5 Master divert control unit..................................................................................................................5 2.6 Indicating transmitters.......................................................................................................................6 2.7 K-Patents digital divert control unit specifications............................................................................7

3

MOUNTING...........................................................................................................................................8 3.1 Wiring ...............................................................................................................................................8

4

START-UP ...........................................................................................................................................12 4.1 Divert control unit start-up ..............................................................................................................12 4.2 Divert control system trimming.......................................................................................................12

5

CALIBRATION....................................................................................................................................13 5.1 Refractometer concentration measurement .....................................................................................13 5.2 Refractometer activation for divert control .....................................................................................13 5.3 Signal difference alarm ...................................................................................................................14 5.4 Low alarms......................................................................................................................................14 5.5 Refractometer malfunction alarm ....................................................................................................14 5.6 Prism wash ......................................................................................................................................14 5.7 Divert decision rules........................................................................................................................15

6

MAINTENANCE .................................................................................................................................17 6.1 Information flow..............................................................................................................................17 6.2 Divert control circuit boards ...........................................................................................................18 6.3 Diagnostic messages........................................................................................................................23 6.4 Diagnostic lights..............................................................................................................................23 6.5 Push-button assembly......................................................................................................................24 6.6 Fuses................................................................................................................................................24

7

DIVERT CONTROL LOGIC ...............................................................................................................25 7.1 Block diagram .................................................................................................................................25 7.2 Logical diagrams .............................................................................................................................26 7.3 Safety Decision Logics....................................................................................................................28

8

OPTIONAL CONFIGURATIONS.......................................................................................................30 8.1 Remote divert control unit...............................................................................................................30 8.2 Equipment .......................................................................................................................................30 8.3 Remote divert control unit in the control room ...............................................................................31 8.4 Wiring and mounting.......................................................................................................................32 8.5 Serial output ....................................................................................................................................34 8.6 Current output signal .......................................................................................................................34 8.7 External DC power supply ..............................................................................................................34

9

DIVERT CONTROL UNIT PARTS LISTS.........................................................................................35 9.1 Divert control unit and optional remote divert control unit.............................................................35 9.2 Remote divert control unit...............................................................................................................36

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

2

2. GENERAL INFORMATION The K-Patents Digital Black Liquor Divert Control System DD-01 provides a divert signal preventing black liquor with dangerously low solids to reach the black liquor burners. The system is built strictly according to the principles of Recommended Good Practice "Safe Firing of Black Liquor in Black Liquor Recovery Boilers" (BLRBAC August, 1982 and revisions April, 1991, and March, 2001). 2.1. DIGITAL DIVERT CONTROL SYSTEM DD-01

Figure 2.10

Complete Digital Divert Control System DD-01

The system consists of the following parts (Figure 2.10): Two K-Patents Process Refractometers PR-01-S (A & B) are installed in series in the main black liquor line. Each refractometer is complete with a Sensor, an Indicating transmitter and Interconnecting cables. Each refractometer provides also a 4-20 mA % solids output signal not used by the divert control system. The Divert Control Unit DD-01 is contained in one enclosure with the same dimensions as the refractometer Indicating transmitter enclosure. The control unit includes: an operator panel control logics contact outputs for prism wash, warnings, alarms and black liquor diversion Two isolation valves HIMP-2 (optional) for the refractometers above to allow removal of the refractometers from a pipe with full flow and pressure. The isolation valve includes a prism wash nozzle and two check valves (one for prism wash, one for stuffing box flush). A roofed mounting plate to mount the two Indicating transmitters and the Divert Control Unit together. Two steam valves with steam traps for prism wash (pneumatic + solenoid valves). Two hand valves (one for prism wash, one for stuffing box flush). One alarm horn (supplied by the customer). Note. BLRBAC (The Black Liquor Recovery Boiler Advisory Committee) recommends a spare sensor to be maintained in stock on-site. INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

3 2.2. OPERATOR PANEL

3

7

4 5

Figure 2.20

6

The operator panel.

The operator panel has a clear layout and the operator can see all information at one glance. The divert decision is controlled from the operator panel which provides doubled security, since all information is simultaneously shown both as LED indication in the Divert Control Unit and as a diagnostic messages in the Indicating Transmitters (Figure 2.20). Each refractometer has a green OPERATING light (1), so the operator knows when he can rely on the refractometer measurement. A refractometer will influence the divert decision only when the green OPERATING light is on. A malfunctioning refractometer is automatically taken out of operation. One green indicator light SAFE% SOLIDS (2) is based on the two refractometers and the divert decision rules (Section 5.7). One red DIVERT light (3) that will be switched on when the SAFE% SOLIDS goes off. The DIVERT light indicates divert status of the divert relay. The divert relay has an output switch contact, for use in the Black Liquor Firing Tripping Logic. The relay is OFF in the DIVERT position, because a power failure will give a DIVERT decision. A lockable OVERRIDE/AUTOMATIC switch (5) and a red OVERRIDE warning light (4) is ON always if switch in OVERRIDE position. If the SAFE% SOLIDS goes OFF and this switch is in the OVERRIDE position, then the OVERRIDE light is lit instead of the DIVERT light. One RESET push-button (6) for the DIVERT action. The DIVERT action always has to be manually reset. If the override switch is in Automatic position and SAFE% SOLIDS is off, the DIVERT action cannot be reset. One EMERGENCY DIVERT push-button (7) to manually initiate DIVERT in an OVERRIDE or emergency situation. The DIVERT light is lit also after manual divert action. The EMERGENCY DIVERT button has a protective hinged cover, to prevent inadvertent use. Two indicator lights (8) for the divert valve status TO BY-PASS/TO BURNER from microswitches on the valve. For intermediate valve positions both lights are off. A row of four alarm lights (9) that indicate black liquor SOLIDS WARNING (at 60%), black liquor SOLIDS ALARM (below 58%), refractometer reading more than 2% absolute difference and refractometer malfunction.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

4 A light test button (10) switches all 11 lights on. An alarm reset button (11) resets the alarm lights. For normal operation the operator panel has four green lights on (A OPERATING/B OPERATING/ VALVE TO BURNER/SAFE% SOLIDS). 2.3. ALARMS The divert control system has four alarms, audible and indicating: 1. 2. 3. 4.

Black liquor SOLIDS WARNING, yellow light (60% or below) Black liquor SOLIDS ALARM, red light (58% or below) Refractometers reading more than 2% absolute DIFFERENCE, yellow light Refractometer MALFUNCTION, yellow light

The alarms 1, 2 and 4 are initiated by either refractometer. System contains also optional alarms, see wiring drawing 3.11. The operator panel contains four indicator lights and an ALARM RESET button. The reset button will silence the audible alarm, but the visual indication will remain until the condition has returned to normal. To avoid unnecessary alarms the following interlocks are implemented: -

A refractometer can initiate an alarm only when it is operating. Alarm 4 can be initiated only if both refractometers are operating.

The parameters (2%, 58% and 60%) are default settings, which can be changed from the Indicating transmitter keyboard (Sections 5.3 and 5.4). The parameter for 2% can be decreased and the parameter for 58% and 60% can be increased. 2.4. PRISM WASH For K-Patents Process Refractometer, the need of prism wash is reduced and even in some cases eliminated. The prism keeps clean due to the probe design features: -

The prism is flush mounted in a surface deflecting the black liquor main flow, which causes a strong mechanical cleaning action.

-

The prism has the same temperature as the black liquor.

In any case, however, an automatic regular prism wash provides an efficient check that the refractometer reacts. A steam wash of 3 seconds every half hour should be sufficient. Automatic single (one-of-two) diversion will occur if either of the refractometers is in wash cycle. The Divert Control Unit contains two relays for prism wash, WASH A and WASH B. To follow the BLRBAC recommendation not to wash both prisms at the same time, there is an interlock. If both refractometers try to wash simultaneously, one will display "WAIT" and perform the wash when the other has finished. K-Patents recommends to use a steam trap instead of preconditioning valve to remove condensate from the steam line. The wash times can be seen pressing soft keys "Display"/"System configuration"/"Wash times". To change the wash times, see Section 5.6.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

5 2.5. MASTER DIVERT CONTROL UNIT

Figure 2.50 indications.

Operator’s panel and functions of the master divert control unit in the field with LED

1. Black liquor SOLIDS WARNING (at 60%), Black liquor SOLIDS ALARM (below 58%), Refractometer reading more than 2% absolute difference, and Refractometer malfunction). 2. Each refractometer A and B has an OPERATING green light, A refractometer will influence the divert decision only when the green OPERATING light is on. A malfunctioning refractometer is automatically taken out of operation. 3. One green indicator light SAFE% SOLIDS, based on the two refractometers and the divert decision rules. 4. A red OVERRIDE warning light is on always if the override switch is switched on.

INSTRUCTION MANUAL FOR DD-01

5. One red DIVERT light that will be switched on when the SAFE% SOLIDS goes off. The DIVERT light indicates divert status of the divert relay. 6. Two indicator lights for the divert valve status. TO BY-PASS/TO BURNER from microswitches on the valve. For intermediate valve positions both lights are off. 7. A lockable Override/Automatic divert switch 8. A DIVERT RESET push-button. 9. An EMERGENCY DIVERT push-button. 10. A light test button switches all 11 lights on. 11. An alarm reset button resets the alarm lights.

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

6 2.6. INDICATING TRANSMITTERS An Indicating transmitter in a Divert Control System is identical (both hardware and software) to a standard transmitter described in the PR-01-S Instruction manual.

1

3 2

A

C ONC

°C P R O C E S S T E M P E R A T U R22.1 E T E S T 109.3 In d iv e r t c o n tr o l o p e r a tio n R em oved S ta r t fr o m d iv p r is m C a lib r a te c o n tr o l wash

A

Figure 2.60

B 8

9

4

5

6

1

2

3

0

.

-

4

D

C

7

5 D is p la y

K -PT E N T S P R O C E S S IN S T R U M E N T S

ENTER

RESET

The Indicating transmitter.

The display, Figure 2.60, will give the following additional information pertinent to the Divert system: 1. A or B in the upper right corner indicates that the transmitter is OPERATING in the divert system as refractometer A or B, Figure 2.10. If a or b is displayed instead, the refractometer is removed from divert control operation. (If the upper right corner is empty, see Section 5.2). For A or B the corresponding green OPERATING light, Figure 2.20, is on, for a or b it is off. If you see a ? in this corner, see Section 5.2. 2. A softkey (B) defined by "Remove from divert control" or alternatively "Restore to divert control". The visible effects of pressing "Remove" for refractometer A is that the soft key changes to "Restore", A switches to a, and the green OPERATING light goes off. Further the "Remove" soft key disappears from refractometer B, because B must not be removed if it is the only refractometer in operation. Note. Always press "Remove" for a refractometer before making service or switching the power off.

INSTRUCTION MANUAL FOR DD-01

3. The "Normal operation" message is substituted by "In divert control operation" or "Removed from divert control". Those messages may change to "Solids warning" or "Solids alarm" at low solids. An additional error message may occur: ** Divert control fault ** combined with a ? in the upper right corner, see Section 6.3. 4. The softkey "Display" (D) leads via "System configuration" (C) to "Divert control system" (D) which gives the following information: Refractometer difference alarm limit in % solids Solids warning limit in % solids (default value 60%) solids alarm limit in % solids (default value 58%) Divert rule and SW1/SW2 positions (Section 5.7) 5. The softkey "Calibrate" (C) gives possibilities to set up for divert control and calibration, see Chapter 5.

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

7

2.7. K-PATENTS DIGITAL DIVERT CONTROL UNIT SPECIFICATIONS Model:

DD-01

Enclosure:

IP66 Nema 4X, dimensions 226 x 267 mm (8.91 x 10.5 in)

Supply:

24 V DC, provided by the Indicating transmitters

Ambient temperature:

max 45 °C (113 °F)

Accessory:

Roofed mounting plate for the Divert Control Unit and 2 Indicating transmitters, Figure 2.60.

Material:

AISI 316, dimensions 916 x 488 mm (36 x 19.2 in)

Figure 2.70

Divert Control Unit Mounting Plate: Dimensions (mm/in)

Figure 2.71

Divert Control Unit and Indicating Transmitter Enclosures: Dimensions (mm/in)

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

8

3. MOUNTING For mounting of the process refractometer and the isolation valve, consult the separate Refractometer PR-01-S(-EX/FM) Manual. 3.1. WIRING Wiring for the complete system, see Figure 3.10 and Figure 3.11 which describe also all cables and how each cable is connected. The cables 1 and 2 are included in the delivery. The terminal strip positions of the Divert Control Unit are specified in Figure 3.11 and Figure 3.12.

Figure 3.10

Divert Control System Wiring Cables and Connections

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

9

Figure 3.11

Divert Control System Wiring and Connections

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

10

Figure 3.12

Cable connections

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

11

RN2

SW 12345678

C16

X2

IC8

IC25

IC21 C38

IC27

D13

K2

8 9 10 11 12 13 14

8 9 10 11 12 13 14

15 16

SERIAL BUS A

SERIAL BUS B

EXT24V

D17 D18

D23

D24

D25 R23

D26 R24

C49

R21 R22

D27

1A

RE1

V1

18

LN

SGND

R28

D30 RE2

19

AC-POWER

RE3

RE4

V4 V3

K5

17

D28 C51 R27

C50 R25 R26 D29

TP4

D31 V2

K4

C41 R12 R13 C42

R16

D2

F2

C40

D14 K3

IC30 L1

R11

RN7

D12

D9

TP3

C26

IC22 R9

C36

SWGND

R15

R14

IC19

C25 D16

R10

D8

K1

IC16

F1

D11

D20 D21 D22 C48 D19 R17 R18 R19 R20

C47

IC23

D7

C35 C52

IC29

IC13

C21

RN5

C33 C34

IC26

D6 D10

1A

C46

D5

C22

D15

C43

C31

R8 C30

C37

C23 1

IC11

C29

IC14 C44

C32

IC18

R7

RN6

IC28

C24

IC12

C19 C20

D1 C45

J2

C27 X1IC17 C28

RN4

GND

IC24

IC5 IC15

D4

IC20

IC4

D3

IC9

C14 IC1

TP2

C13

IC7

IC10

J1

C7

C18

C1 R2 C2 R3 C3 R4 C4 R5 C5 R6 C6

R1

C15

IC6

RN1

+5V

C39

C11

C17 SW1

IC3

C10

TP1

CONTROL UNIT

C12

IC2

C9

C8

PR-7310 Rev.C DIVERT

RN3

K-PATENTS

K6

20 21

22 23

WASH A

WASH B

RE5 V6

K8

RE7

RE8

V8

V5 K7

RE6

V7 K9

V9 K10

K11

K12

D32 63mA

63mA

F3

F4 K13

K14

VALVE 35 36 POSITION37 38 39 40 BYPASS BURNER HORN SOLIDS SOLIDS NORM. OVERRIDE REF.DIFF. WARN. ALARM DIVERT 24 25

26 27

28 29 30

31 32

33 34

DANGER HIGH VOLTAGE Figure 3.13

Divert control circuit board, layout.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

12

4. START-UP For refractometer start-up consult the separate Refractometer PR-01-S(-EX/FM) Manual and the Mounting and start-up check list. 4.1. DIVERT CONTROL UNIT START-UP 1.

Check the wiring and supply voltage. Note: Before the power is switched on, the DIVERT output relay is in DIVERT position.

2.

Switch the power on for both Indicating transmitters. The control system is now in the DIVERT mode, and the red DIVERT light is on.

3.

Press the LIGHT TEST button. All eleven lights should switch on.

4.

The upper right corner of the Indicating transmitter displays should now state a or b respectively. If not, see Section 5.2. If the message is "Removed from divert control" the refractometer is ready to "Restore to divert control", softkey B. If the message is "Solids warning" or "Solids alarm" then "Restore" provokes an alarm. Press the ALARM RESET button. For any other message, see Section 6.3.

5.

Observe that the VALVE STATUS lights follow the position of the valve. Now the Divert Control System is set for normal monitoring operation.

6.

Check that the prism wash is working. Press the "Start prism wash", softkey A.

7.

When the SAFE % SOLIDS has turned on and also the other conditions for safe boiler operation are satisfied, the DIVERT can be turned off using the RESET button.

4.2. DIVERT CONTROL SYSTEM TRIMMING During the trimming of a new system, it is recommended to keep the key in the OVERRIDE position. When the key is in the OVERRIDE position, the DIVERT action has to be initiated manually using the EMERGENCY DIVERT button. This should be done when the green SAFE %SOLIDS light turns off. The trim procedures are described in Chapter 5, the measurement calibration in Section 5.1 and the prism wash in Section 5.6. The key should be turned to the AUTOMATIC position only after it has been decided that sufficient experience has been gained.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

13

5. CALIBRATION The K-Patents Divert Control System is calibrated by the manufacturer. This chapter contains instructions how to make the fine adjustment of the system. 5.1. REFRACTOMETER CONCENTRATION MEASUREMENT For refractometer calibration consult also the separate Refractometer PR-01-S(-EX/FM) Manual. The CONC% displays of the two Indicating transmitters have to show the same value. If there is a difference, this can be eliminated by changing the Bias for one of the refractometers. Key in the sequence Calibrate / Parameters / CONC(RI) / Parameters / Bias. Comparison with sample determination can decide which one should be corrected. Example: If the Indicating transmitter of A displays CONC% = 63.2% and B displays CONC% = 63.8%, the difference can be eliminated e.g. by lowering B by 0.6%. Read bias from the display of refractometer B. If bias = 52.923 then enter a new bias = 52.323. Due to its digital measurement principle, the readings of the K-Patents Process Refractometer do not drift by time. Frequent recalibrations based on off-line moisture analysis must be avoided, as they will introduce random fluctuations to the refractometer readings. If the concentration reading is noisy, the damping can be increased. Enter Calibrate / Parameters / CONC(RI) / Damping time. The Damping time is the time in seconds for the signal to reach half of its final value after a step change. Increase the damping time in small steps, and wait for the result. 5.2. REFRACTOMETER ACTIVATION FOR DIVERT CONTROL When a refractometer is activated for Divert control, the upper right corner of the display shows alternatively A, a, B, b or ?. If the corner is blank the divert function must be activated by pressing the sequence Calibrate/Parameters/Divert control/Divert control and select "1 Activated". The program has to be version 4.0 or higher, otherwise "8 Divert control" is missing from the CALIBRATE menu. The program EPROM has then to be changed to an up-dated version. The decision to display A (a) or alternatively B (b) is not programmed, it depends on to which SERIAL BUS port in the Divert unit (Figure 3.13) the Indicating transmitter is connected. If a Divert activated refractometer is used in another type of application, the divert function has to be deactivated by selecting "0 Not activated". After de-activation all references to Divert functions disappear except "8 Divert control" in the CALIBRATE menu. Note. If a message DIVERT CONTROL FAULT and a ? appear on the IT-R display, the reason is one of the following: 1.

Cables between the IT-R and the terminals 8-14 on the DD-01 are not properly connected. Reconnect to fix.

2.

Communication 485 component IC 17 (A) or IC 19 C (B) is broken on the PR-7310 board inside the DD-01. Replace board.

3.

Communication 485 component IC 1r is broken on the PR-7010 board inside the IT-R. Replace board.

4.

Dip switch 3. is in the “up” position which means that the PR-7310 card is configured to work in the remote mode. Change the dip switch back to low (=off) position.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

14 5.3. SIGNAL DIFFERENCE ALARM According to BLRBAC, if a difference of 2% solids (absolute value) or greater exists between refractometer readings, an alarm shall be activated. The alarm limit 2% can be changed from the keyboard using the sequence Calibrate/Parameters/Divert control/Ref. difference limit. If the deviation alarm trips seem too frequent, it may help to increase the signal damping, Section 5.1. Note. If the two refractometers have different limit values, the lower value is used by alarm system. 5.4. LOW ALARMS The low alarm limits are set from the keyboard of the Indicating transmitter. Enter sequence Calibrate/Parameters/Divert control. The menu will show “3 Low conc warning limit” and “4 Low conc divert limit”. The latter has a double function: Both LOW SOLIDS ALARM and DIVERT limit. The Indicating transmitter display will carry the messages “Solids warning” and “Solids alarm” when the corresponding alarms occur. Note. The alarm limits are set separately for the two refractometers. Each refractometer gives an alarm according to its own settings. 5.5. REFRACTOMETER MALFUNCTION ALARM The built-in intelligent diagnostics of K-Patents Process Refractometer provides a tight control of the operation. A full test cycle is completed with an interval less than one second. A description of the microprocessor implemented diagnostics is given below. For details consult the Instruction Manual of the refractometer PR01-S. Only errors classified as Equipment malfunctions will cause alarm and removal from the Divert control system. Process related faults will only cause a message in the Indicating transmitter display. See also Section 6.3 for additional diagnostics. The most important test is to check the signal coming from the digital image sensor during measurement. Improper function of light source, optical components, image sensor and sensor driver are recognized by this test. The compensation for temperature measurement is checked, both the temperature element and the A/D converter. The cable between Sensor and Indicating transmitter is checked using a check sum method, thus recognizing short circuits, open circuits and excessive disturbances. The microprocessor system has also a self-checking test program to ensure the proper operation of the CPU and the memories. The constants in the EEPROM memory are tested to be within strict limits of acceptance. The performance of the microprocessor is of critical importance for the measurement control. A separate hardware watch-dog circuit ensures the proper microprocessor operation by checking that the microprocessor regularly sends out a predetermined pulse sequence. Another hardware circuit checks that the supply voltage to the microprocessor is within safe limits, to prevent any brownout stray output pulses. 5.6. PRISM WASH A prerequisite for a proper function of the divert system, is that the prism wash works. The TEST value in the display should increase at least 20 steps during WASH, provided TEST is not close to its maximum value 248. See Sections 8.1, 8.5 and 9.2 in PR-01-S Instruction Manual.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

15 WASH TIMES The wash times can be seen by pressing Display/System configuration/Wash times. The values set at delivery are the following: Preconditioning = 0 seconds Wash time = 3 seconds Recovery time = 30 seconds Interval = 20 min The wash times are changed by pressing the sequence Calibrate/Parameters/Prism wash. Note maximum wash time is 30 seconds and maximum recovery time 30 seconds. WASH CHECK This function can be defined from the prism wash menu: Calibrate/Parameters/Prism wash/Wash test. A prism wash is accepted if: a.

TEST exceeds “TEST limit”

b.

TEST increases more than “TEST difference”

The default values of “TEST limit” and “TEST difference” are zero (0), which makes the wash check inactive. If the wash is not accepted, the diagnostic message will be “Prism wash failure”. A “Wash retries” parameter can also be set to repeat the wash if the wash check fails. The default value is zero (0). WASH STOP Wash stop function can be defined from the prism wash menu. Wash can be prevented when the process temperature is below the set limit, thus indicating that the pipe is not in use. To activate the “wash stop” key sequence: Calibrate/Parameters/1. Prism wash/Wash stop/1. Active and set the temperature limit. The default value for wash stop is inactivate. When the wash is not accepted the diagnostics message is “Wash stop/temp. limit”. EXTERNAL WASH STOP An input switch can be configurated to an external wash stop to prevent the prism wash when the corresponding input switch is connected. “External wash stop”-message will show when automatic wash is activated from the soft keys. The input switch can be set to protect the refractometer e.g. if the process is stopped. AUTOMATIC SINGLE DIVERSION CONTROL DURING PRISM WASH CYCLE Automatic single (one-of-two) diversion control will take place if either of sensors are in prism WASH cycle. 5.7. DIVERT DECISION RULES TWO REFRACTOMETERS IN OPERATION: BLRBAC states the following: For the solids measurements, two refractometers in series must be used. When both refractometers are in service, the requirement for an automatic black liquor diversion can be satisfied by either of the following options: 1.

If either refractometer reads dissolved solids content 58% (default) or below, an automatic black liquor diversion must take place.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

16 2.

When both refractometers read dissolved solids content 58% (default) or below, an automatic black liquor diversion must take place.

Either option is satisfactory. The rules are listed in decreasing order of security. Only rule 1 satisfies the high safety requirements set by BLRBAC, August, 1982. On the other hand, the probability of false trips decreases with decreasing safety. It means that if false trips are too frequent, the rule 2 may be preferred at the cost of safety. The rule 2 has later been accepted by BLRBAC. A third conceivable alternative is to base the decision on only one refractometer (the master) and use the other refractometer (the slave) for comparison only (and difference alarm). Concerning security and false trips, this rule is a compromise between rules 1 and 2. The divert decision rule is selected by the switch SW on the divert control board (Figure 3.13). ON position is upwards.

Switch SW SW1 SW2 OFF OFF ON OFF OFF ON ON ON Table 5.70

Rule One-of-two (BLRBAC) A master, B slave B master, A slave Two-of-Two

Rule 1 Rule 2

Divert decision rule selection.

ONLY ONE REFRACTOMETER IN OPERATION: When only one instrument is IN OPERATION the divert action takes place if this instrument reads 58 % or below. The status of SW (Table 5.70) has no influence on the divert decision in this case. NO REFRACTOMETER IN OPERATION: If both instruments are out of operation (due to malfunction or maintenance), then according to BLRBAC divert action must take place. See also Section 8.7 about external DC supply. REMOTE DIVERT SWITCH CONFIGURATION Switch SW SW 3 OFF ON

Rule DD-01 normal operation Remote divert card activated See Section 8.8.

See Section 5.2 if you have on the screen the message DIVERT CONTROL FAULT.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

17

6. MAINTENANCE As the Divert Control System is a pure digital system, no special maintenance is needed. The LIGHT TEST button on the operator panel (Figure 2.50) sends a signal to the microprocessor, and the microprocessor switches all 11 LED lights on as long as the button is pressed. This way not only the lights but also the processing system is checked. To assist the identification of a faulty component, the information flow and the circuit diagrams are given in Sections 6.1 and 6.2. Also the logic diagrams of Chapter 7 may be of help. 6.1. INFORMATION FLOW The power and information flow of the total Divert system is shown by Figure 6.10. Additional information about the cable connections is found in Figures 3.10, 3.11 and 3.12.

Figure 6.10

Information and power flow.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

18

6.2. DIVERT CONTROL CIRCUIT BOARDS The component lay-out of the divert control circuit board is shown by Figure 3.12 and the circuit diagram by Figures 6.20 to 6.25.

Figure 6.20

Operator panel board, component layout.

Figure 6.21

Operator panel PR-7311 circuit diagram, page 2 of 2

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

19

Figure 6.22

Operator panel PR-7311 circuit diagram, page 1 of 2.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

2

TXD0 RXD0

TXD1 RXD1

INT1

+5V

1

R8

3K32

2

1

10R0

6 WDI 1 2 VCC

+5V

GND 3 48

RESET

C25

2 100n

1

7

10K0

R7

IC18 MAX699

2

RN1 1

+5V

32.0MHz

X1

C26

RN4

1

1 1 1 1 1

2 100n

C24

6 8 7 9 5

1

C22

2 100n 2 100n

1

10K0

RN5 RN5 RN5 RN5 RN5

RN5 2

10K0

RN5

1 RN5 4 1 3

10K0 1 RN4 4 1 6 1 RN4 5 RN4 3 1

C23

+5V

2 100n

1

14 VCC Osc. 1 N.C. OUT 8 7 GND

1

+5V

P2.7 P2.6 P2.5 P2.4 P2.3 P2.2 P2.1 P2.0

INT4 INT3 INT2 INT1 INT0

T0IN T0OUT T1IN T1OUT

HOLD HOLDA NCS ERROR PEREQ

RESIN PDTMR NMI TEST READY

2 22 43 63 VSS 65 84

1 23 VCC 42 64

A19 A18 A17 A16 AD15 AD14 AD13 AD12 AD11 AD10 AD9 AD8 AD7 AD6 AD5 AD4 AD3 AD2 AD1 AD0

UCS LCS P1.7 P1.6 P1.5 P1.4 P1.3 P1.2 P1.1 P1.0

RESOUT S2 S1 S0 ALE BHE RD WR DEN DT LOCK

83 82 81 80 79 77 75 73 71 69 67 62 78 76 74 72 70 68 66 61

30 29 19 20 21 24 25 26 27 28

38 8 9 10 6 7 4 5 11 16 15

CLOCKOUT 44

80C186EB

51 52 CTS0 TXD0 53 RXD0

49 50 54 56 55 59 58 57

35 34 33 32 31

46 45 48 47

13 12 60 3 39

37 36 17 14 18

41 CLKIN 40 OSCOUT

IC15

16bit MICROPROCESSOR

+5V

AD19 AD18 AD17 AD16 AD15 AD14 AD13 AD12 AD11 AD10 AD9 AD8 AD7 AD6 AD5 AD4 AD3 AD2 AD1 AD0

SRLY ISOSW SSER2 SDISP

RESOUT

RESET

AD7 AD6 AD5 AD4 AD3 AD2 AD1 AD0

AD15 AD14 AD13 AD12 AD11 AD10 AD9 AD8

AD19 AD18 AD17 AD16

1Q 2Q 3Q 4Q 5Q 6Q 7Q 8Q

1Q 2Q 3Q 4Q 5Q 6Q 7Q 8Q

1Q 2Q 3Q 4Q 5Q 6Q 7Q 8Q

74HC573

1 OC 11 C 2 1D 3 4 2D 3D 5 4D 6 5D 7 6D 8 7D 9 8D

IC10

74HC573

1 OC 11 C 2 1D 3 2D 4 5 3D 4D 6 5D 7 6D 8 7D 9 8D

IC7

74HC573

1 OC 11 C 2 1D 3 2D 4 3D 5 6 4D 5D 7 6D 8 7D 9 8D

IC3

19 18 17 16 15 14 13 12

20 10

19 18 17 16 15 14 13 12

20 10

19 18 17 16 15 14 13 12

20 10

C9

C13

C18

A7 A6 A5 A4 A3 A2 A1 A0

2 100n

1

+5V

A15 A14 A13 A12 A11 A10 A9 A8

2 100n

1

+5V

A18 A17 A16

2 100n

1

+5V

A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

A18

A0

C8 14

HC32

1

IC2

38 37 36 35 34 33 32 31 29 28 27 26 25 24 23 22 21

3 4 5 6 7 8 9 10 12 13 14 15 16 17 18 19

11 30

40

11

8

6

O15 O14 O13 O12 O11 O10 O9 O8 O7 O6 O5 O4 O3 O2 O1 O0

27C210

NC A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1 A0

2 20 CE OE 39 PGM

IC8 +5V 1 VPP

13

HC32

1

12

IC2

9

HC32

1

IC2

10

5 7

2 100n 4

1

64K x 16bit EPROM

INSTRUCTION MANUAL FOR DD-01 C14

AD15 AD14 AD13 AD12 AD11 AD10 AD9 AD8 AD7 AD6 AD5 AD4 AD3 AD2 AD1 AD0

2 100n

1

+5V

A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1

1 26 2 23 21 24 25 3 4 5 6 7 8 9 10

IO8 IO7 IO6 IO5 IO4 IO3 IO2 IO1

55257

A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1 A0

IC4

55257

IO8 IO7 IO6 IO5 IO4 IO3 IO2 IO1

IC5

A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1 A0

20 CE 22 OE 27 W

1 26 2 23 21 24 25 3 4 5 6 7 8 9 10

20 CE 22 OE 27 W

32K x 8bit SRAM

Figure 6.23 32K x 8bit SRAM

+5V

AD7 AD6 AD5 AD4 AD3 AD2 AD1 AD0

100n

C10

+5V

AD15 AD14 AD13 AD12 AD11 AD10 AD9 AD8

2 100n

C11

+5V 1

AD0-15

A0-9

19 18 17 16 15 13 12 11

14

28

19 18 17 16 15 13 12 11

14

28

RD WR

20

Divert control board PR-7310 circuit diagram. Page 1 of 3.

DOCUMENT/REVISION: IMD 1/5

Effective: June 20, 2005

10 12 14 40 44 46

SSER2 RESOUT

RD WR

A1-3

1 2 3 4 5 6 7 8

2

16 15 14 13 12 11 10 9

R25

EMERGENCY DIVERT

DIVERT RESET

OVERRIDE

1

100n 2

D30

ALARM RESET

1

1

C50

R28

3K3

3K3

SA5.0

LAMP TEST

SW8

SW1

2

1

2

2

R27 2

1

500R

SA5.0 2

D31

1 1N4007

2

D29

1 F4

2

C51

R6

2

1 TP4 2

2 100n

1

1

D28

2

D27

1

1

2

SWGND TEST POINT

R5

R4

C6

+5V

1

R3

C5

1

2

1

C4

1

1

1

C2

R1

2 100R1 1

C3

R2

C42

2 100n

1

C41

2 100n

1

+5V

1

C1

KN6

KN5

KN4

KN3

KN2

KN1

RD

ISOSW

2 2 2 2 2 2 100n 100n 100n 100n 100n 100n

1

1

2

2

+5V

7

VO2 6 GND 5

VO1

VCC

HCPL2731

3 4 22+

1 1+ 2 1-

IC29 8

4 VCC 1 GND

NME0505D

5 VOUT 7 0V

KN1 KN2 KN3 KN4 KN5 KN6

AD0 AD1 AD2 AD3 AD4 AD5 AD6 AD7 A1 A2 A3

DIP8 DIP7 DIP6 DIP5 DIP4 DIP3 DIP2 DIP1

D0 D1 D2 D3 D4 D5 D6 D7

1

1 74HC05

1

8

9

7

21

2

X2 15 DTR 16 RTS 6 TXD 5 INT 13 RXD RI 10 CTS 14 11 DSR 12 DCD

X1

VSS

VCC

IC23

20 RD 19 18 WR CS 17 RESET

22 A0 23 24 A1 A2

25 26 27 28 1 2 3 4

IC9

20 1 & G1 EN 19 10 G2 18 2 Y1 A1 17 3 Y2 A2 16 4 A3 Y3 15 5 A4 Y4 14 6 A5 Y5 13 7 A6 Y6 12 8 A7 Y7 11 9 A8 Y8 HC541

IC6

1 20 & G1 EN 19 10 G2 18 2 Y1 A1 17 3 Y2 A2 16 4 A3 Y3 15 5 A4 Y4 14 6 A5 Y5 13 7 A6 Y6 12 8 A7 Y7 11 9 A8 Y8 HC541

IC1

82510

AD0-15

J1 J1 J1 J1 J1 J1

1N4007 2 D32 1

X14 2

X14 1

BURNER

X13 2

X13 1

R26 2 1

C40

2 100n

1

RN2

1

1

RN1 1 7

RN2 1

500R 3K32

RN2 1 9

RN1 1 6

7 RN2 1 1

6

RN1 1

4

RN2 1

3

8

5 RN1 1

Opto-isol.

RN2 1

5

RN1 1

RN2 1

4

2

RN2

1 F3

2 1 3K32

2 1 1K

BYPASS

1K

R13 2 R12 1

IC28 DC/DC conv. C7

C12

9

C17

1 74HC05

1

IC23

INT1

2 100n

1

+5V

AD15 AD14 AD13 AD12 AD11 AD10 AD9 AD8

2 100n

1

+5V

AD0-18

AD0 AD1 AD2 AD3 AD4 AD5 AD6 AD7

2 100n

1

+5V

8

C16

11

C15

1 74HC05

1

IC23

CTS

RXD

TXD

RTS

1

13 7

100n 2 10

C38

9 12 6 15 5 16 2 19

20 10

2 100n

1

+5V

C31

2 33pF

1

18.432MHz 1 2

X2

C37

1Q 2Q 3Q 4Q 5Q 6Q 7Q 8Q HC273

2 100n

1

+5V

1D 2D 3D 4D 5D 6D 7D 8D

IC20

1 R CLR 11 C1 CP

AD0 8 AD113 AD2 7 AD314 AD4 4 AD517 AD6 3 AD718

2 33pF

1

HC32

C28 D4

12

HCPL2731

GND

VO2

VO1

VCC

IC26

5

6

7

8

3 24 2+

HCPL2731

GND

VO2

VO1

5

3

1 74HC05

1

IC23

1

IC23 1 74HC05

5 VOUT 7 0V

1 1+ 2 1-

IC24 VCC

3 24 2+

IC23 14

1

2

NME0505D

1 1+ 2 1-

5

6

7

8

+5V

D3

+5V

1k00

IC27 DC/DC conv.

1

2

4 VCC 1 GND

2 100n

1

1 74HC05

1

RN7

1

1K0

3

2

RN1

2

Opto-isol.

WR

5 1 RN7 1 4 RN7 1 3 RN7 1 2

RN3 1 3

RN3 1 2

Opto-isol.

3

RN6

1K0 2 1 RN6 1 4

IC2

C52 2 100u

1

TP3

C33

TXDI

RXDI

11

10

12

6

5

13

C35

4

2

RTSI

1

2 100n

1

5VSER

2 100n CTSI

SA5.0

D9

LTC485

5

6

7

8

C30

C1+

T

T

C2-

C2+

C1-

R

R

VCC +9V -9V OFF GND

8

9

15

14

17 3 7 18 16

2 100n

1

2 100n

IC25 LT1180

DO GND

DE

DO

VCC

C27

1

1

D6

1

1

C34

SGND

SD

RD

UARTS

UACTS

2 100n 2 100n

1

3 K2A

4 J2

1 J2

2 J2

3 J2

6 J2

5 J2

(10)

1 K2A (8)

2 K2A (9)

B

3 K1A (10)

1 K1A (8)

2 100n

1

A 2 K1A (9)

C32

SER1+

D5 2 SA5.0 SA5.0

D8

SER1-

2 SA5.0 SA5.0

C36

2

1

2

D7

SER0+

5

SER0-

6

1

+5V

7

8

+5V

GND

DO

DO

VCC

LTC485

IC17

IC19

DI

DE

RE

RO

4 DI

3

RE

RO

4

3

2

1

1 SGND 2 TEST POINT

2

2 100n

TXD1

2

1

TXD0

RXD0

RTS

D12

1

1

2

1

C39 1

6

4

5 RN3 1 1k00

2 D10

RN6

1

2 10R0 1

1 4

RN3 3 RN6 1 5 1

INSTRUCTION MANUAL FOR DD-01 R11

Figure 6.24 POWER

RESET

21

Divert control board PR-7310 circuit diagram. Page 2 of 3.

DOCUMENT/REVISION: IMD 1/5

Effective: June 20, 2005

.

1

J1 47 J1 49

A (14) K1C 2 B (14) K2C 2

(16) K3 2

(15) K3 1

(11) K2B 1 B (12) K2B 2 (13) K2C 1

P

GND

EXT24V

SR224V

2

VIO24V

11

8

6

3

SR124V

HC32

IC16

13

HC32

1

IC16

14

HC32

1

IC16

12

10 7

(11) K1B 1 A (12) K1B 2 (13) K1C 1

.

2 100n

1 C21

9

5

WR

+5V

4

SDISP

RESET

1

2

HC32

IC16

1

2

AD8 AD9 AD10 AD11 AD12 AD13 AD14 AD15

AD0 AD1 AD2 AD3 AD4 AD5 AD6 AD7

AD0 AD1 AD2 AD3 AD4 AD5 AD6 AD7

1

2

1

1

2

D17

D16 2 1 1N4007

IC14

1 CLR 11 CP 3 1Q 1D 4 2Q 2D 7 3Q 3D 8 4Q 4D 13 5Q 5D 14 6Q 6D 17 7Q 7D 18 8Q 8D HC273

1 CLR 11 CP 3 1D 1Q 4 2D 2Q 7 3D 3Q 8 4D 4Q 13 5D 5Q 14 6D 6Q 17 7D 7Q 18 8D 8Q HC273

IC11

IC21

1 CLR 11 CP 3 1D 1Q 4 2D 2Q 7 3D 3Q 8 4D 4Q 13 5D 5Q 14 6D 6Q 17 7D 7Q 18 8D 8Q HC273

D11 D13 D14

1

2

1

R16 4K7

SRLY

R9 4K7

. .

.

2

1

2 1 1N4007 1N4007 D18

1 .

1A

.

F1

2 5 6 9 12 15 16 19

20 10

2 5 6 9 12 15 16 19

20 10

2 5 6 9 12 15 16 19

20 10

.

2

.

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

1 2 3 4 5 6 7 8

+

1 C48

.

Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7

Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7

Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7

1 C49

.

.

+

18 17 16 15 14 13 12 11

18 17 16 15 14 13 12 11

2 2u2 .

SS FRC OSC 15 11 14

1 C43

.

IC30

15K0 1 C46

.

GND

.

.

13 12

FB 10

VOUT 2

2 33n 2 2n2

1 C47

.

4 5

L4962

7 VIN

ULN2803A

D0 D1 D2 D3 D4 D5 D6 D7

RE1 RE2 RE3 RE4 RE5 RE6 RE7 RE8

10 VIO24V DCOM GND 9

IC13

ULN2803A

D0 D1 D2 D3 D4 D5 D6 D7

18 17 16 15 14 13 12 11

VIO24V

DCOM 10 VIO24V GND 9

IC12

ULN2803A

D0 D1 D2 D3 D4 D5 D6 D7

DCOM 10 GND 9

IC22

2 SA26 2 100u 2 33nF

1 D15

.

VIO24V

2 100n

1 C20

.

+5V

.

2 100n

1 C19

.

+5V

.

2 100n

1 C29

.

2

L1 150uH

4K64

.

2 BYV27/50

1 D2

.

+

.

.

.

C45 2 220u

1

1

+

WARN

.

C44 2 220u

1

.

OUT8

OUT7

OUT6

OUT5

OUT4

2

1

TP1 +5V

D1

TEST POINT

1 2

TP2 GND

TEST POINT

1 2

39 J1

38 J1

36 J1

37 J1

35 J1

32 J1

30 J1

28 J1

29 J1

27 J1

26 J1

25 J1

22 J1

20 J1

21 J1

19 J1

SA5.0

+5V

BURNER

VBYPASS

DIVERT

OVERRIDE

SAFE

BOPER

AOPER

MALFUNC

REFRDIF

ALARM

RE1-8

RE8

RE7

RE6

RE5

RE4

RE3

RE2

RE1

VIO24V

2 2 1 R24 4K7

AD0-18

1 R15 2

. .

.

R10 2 4K7 1

1 R14 2

D19

D20

D21

D22

D23

D24

D25

D26 1

8

5

8

12 5

9 8

5

8

5

8

5

8

5

16

1

16

1

16

1

16

1

16

1

16

1

16

8

5

8

1

16

5

. . . .

1 2 2 1 R23 4K7 1 2 2 1 R22 4K7 1 2 2 1 R21 4K7 1 2 2 1 R20 4K7 1 2 2 1 R19 4K7 1 2 2 1 R18 4K7 1 2 2 1 R17 4K7 1

V9 V8 V7

RE8 RE7 RE6 RE5 RE4 RE3 RE2 RE1

2 1 2 1 2

. . . . . .

1 2 1 2 1 2

. . . . . .

1 2 1

V5 V4 V3 V2 P

N

L

V1

INSTRUCTION MANUAL FOR DD-01 . .

Figure 6.25 2 1

+5V

.

F2 1A

V6 2

.

1

3 K4

2 K4

1 K4

2 K5

A WASH

2 K6 1 K5

B WASH

2 K7 1 K6

LINE

SOLIDS WARN.

2 K8 1 K7

SOLIDS ALARM

2 K9 1 K8

DIVERT/NORM

2 K10 1 K9 3 K9

HORN

2 K11 1 K10

REF. DIFF

2 K12 1 K11

NO MALF.

1 K12

22

Divert Control board PR-7310 circuit diagram. Page 3 of 3.

DOCUMENT/REVISION: IMD 1/5

Effective: June 20, 2005

23 6.3. DIAGNOSTIC MESSAGES For diagnostic messages in the Indicating transmitter display, see the PR-01-S manual. The following messages appear only in divert systems: -

"In divert control operation" or "Removed from divert control", Section 2.6.

-

"Solids warning" and "Solids alarm", Section 5.4.

-

** Divert control fault **

This message indicates that there is no communication to the divert control unit, probably cable error, Figure 3.12, cable 2. If the instrument is not applied in a divert control system, de-activate the divert function, see end of Section 5.2. Further the message ** Relay unit fault ** may appear. This indicates that the Relay unit PR-7080 functions are defined, but no Relay unit is connected. Normally a Relay unit is not used in a Divert system because the wash contacts are in the Divert control unit. Clear the relay functions by the key sequence Calibrate/Relay unit and select an "0 Not Defined" for all four relays. For using an optional relay unit, see PR-01-S Manual, section 9.1. 6.4. DIAGNOSTIC LIGHTS The Divert circuit board, Figure 3.12, contains the following diagnostic LEDS: D3

Processor cycles: should flash

D4

Processor reads serial bus: should flash

D10

Serial bus A input: should flash

D11

On if 24 V DC supply from A is OK

D12

Serial bus B input: should flash

D13

On if 24 V DC supply from B is OK

D14

On if external 24 V DC is applied

D19

Wash relay A on

D20

Wash relay B on

D21

Solids warning relay on

D22

Solids alarm relay on

D23

Divert relay on = not DIVERT (Section 2.2)

D24

Horn on

D25

Refractometer difference relay on = difference alarm

D26

Override

D27

Valve to bypass

D28

Valve to burner

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

24

6.5. PUSH-BUTTON ASSEMBLY Before removing the push button or the lockable Override/Automatic switch from the front panel turn the screw 1/4 to the left, Figure 6.50. This will release the contact element.

Figure 6.50

Securing and removal of the contact element.

6.6. FUSES The following fuses are printed on circuit board PR-7130: Fuse F1:

Microfuse IEC 127-3/1

DC Power (24 VDC) main fuse. Protects UL 198G 1A, fast divert electronics againts wrong voltages especially from external DC supply.

Fuse F2:

5 x 20 mm fuse IEC 60127, 1A, fast

AC supply to solenoid valves. Protects cable and coil, if faults appear.

Fuses F3, F4:

Microfuse IEC 127-3/1,

Fuses protect switch of divert valve position UL 198G 63 mA, fast feedback. Any external voltage connected to these circuits causes fuse blow.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

25

7. DIVERT CONTROL LOGIC A logical description of the system is provided as a complement to the previous information about the electronics. 7.1. BLOCK DIAGRAM The block diagram Figure 7.10 shows the connections between the different logical subsystems.

Figure 7.10

Block diagram of the divert control system

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

26 7.2. LOGICAL DIAGRAMS

Figure 7.20

The operation logics.

Figure 7.21

The divert decision logics.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

27

Figure 7.22

The alarm decision logics.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

28

Figure 7.23

The alarm system.

7.3. SAFETY DECISION LOGICS The logical description of the Safety Decision Logics in Figure 7.10 is given by the following tables: - Table 7.30 One - of - two - Table 7.31 A master, B slave - Table 7.32 Two - of - two Note. NOT OPERATING includes the wash cycle. See also Section 5.7. A 58

One-of-two decision rule

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

29

A 58

OPERATING

NOT OP

OPERATING

NOT OP

58 OPERATING

Unsafe

Safe

Safe

Safe

NOT OP

Unsafe

Unsafe

Safe

Unsafe

A master, B slave A 58

OPERATING

NOT OP

OPERATING

NOT OP

58 OPERATING

Safe

Safe

Safe

Safe

NOT OP

Unsafe

Unsafe

Safe

Unsafe

Two-of-two decision rule

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

30

8. OPTIONAL CONFIGURATIONS

8.1. REMOTE DIVERT CONTROL UNIT The remote divert control unit is an option of the digital divert control system DD-01, see Figure 8.20. The remote divert control unit operates as a main unit, which means that the master divert unit is for indication only. If the remote divert control unit is not in operation, the master divert unit in the field operates as a main unit. The remote control unit communicates with the master divert unit in the field through a modem. Connection and wiring is made according to Figure 8.40. For contact terminals see Figure 8.41. Contact terminals 24 and 25 are for communication OK signal. 8.2. EQUIPMENT

Figure 8.20

Complete remote divert control system.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

31 8.3. REMOTE DIVERT CONTROL UNIT IN THE CONTROL ROOM

Figure 8.30

Operator’s panel and functions of the remote divert control in the control room.

The remote divert control unit contains all information for the deviation decision. The operation is clearly indicated with LED lights as follows:

1. A row of four alarms (indicating Black liquor SOLIDS WARNING (at 60%), Black liquor SOLIDS ALARM (below 58%), Refractometer reading more than 2% absolute difference, and Refractometer malfunction). 2. Each refractometer A and B has an OPERATING green light, so the operator knows when he can rely on the refractometer measurement. A refractometer will influence the divert decision only when the green OPERATING light is on. A malfunctioning refractometer is automatically taken out of operation. 3. One green indicator light SAFE% SOLIDS, based on the two refractometers and the divert decision rules. 4. A red OVERRIDE warning light. 5. One red DIVERT light that will be switched on when the SAFE% SOLIDS goes off, providing OVERRIDE is off. The DIVERT light indicates divert status of the divert relay.

INSTRUCTION MANUAL FOR DD-01

6. Two indicator lights for the divert valve status. TO BY-PASS/TO BURNER from microswitches on the valve. For intermediate valve positions both lights are off. 7. A lockable Override/Automatic switch. 8. One RESET push-button for the DIVERT action. The DIVERT action always has to be manually reset. If the override swithc is in automatic position and SAFE% SOLIDS is off, the DIVERT cannot be reset. 9. EMERGENCY DIVERT push-button. 10. A light test button switches all 11 lights on. 11. An alarm reset button resets the alarm lights. 12. Communication to MASTER DIVERT ok, indication light blinking. 13. Power supply ok, indication light on. Note when remote divert in use, master divert unit in the field is for indication only!

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

32 8.4. WIRING AND MOUNTING For wiring of the complete system, see Figure 8.40, which also specifies the cables and connections.

Figure 8.40

Digital Divert Control System with Remote Divert Control Unit Wiring.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

33

Figure 8.41

Remote Divert Control Unit terminals.

Figure 8.42

Digital Divert Control System: Remote Divert Control Unit mounting.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

34 8.5. SERIAL OUTPUT Each Indicating transmitter has a serial output not used by the Divert Control unit. This serial output is selectable RS-232/RS-485 (see PR-01-S Manual) and contains concentration, temperature and error data. It contains also information whether the refractometer is in divert operation or not. Possible uses of the Serial output: To communicate with a computer substituting the Divert Control unit. 8.6. CURRENT OUTPUT SIGNAL Each Indicating transmitter provides a 4-20 mA output concentration signal not used by the Divert system. To calibrate this signal for suitable %Solids range, press Calibrate/Output signal/Current output, see PR-01-S Manual. 8.7. EXTERNAL DC POWER SUPPLY The Divert Control unit may be connected to a DC power supply as a back-up. At AC power failure the refractometers will black-out, but the Divert Control unit will still work. In this case the DIVERT signal can be prevented by turning the key to OVERRIDE. Terminals are 15 (+24VDC) and 16 (ground). The power requirement is 24 VDC, 500 mA. 8.8. DIVERT CONTROL UNIT CARD IN THE REMOTE UNIT In the remote unit the divert control card the third dip switch SW3 must be in the ON position (“up”). See Figure 3.13 and Sections 5.2. and 5.7.

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

35

9. DIVERT CONTROL UNIT PARTS LISTS

9.1. DIVERT CONTROL UNIT AND OPTIONAL REMOTE DIVERT CONTROL UNIT

ltem 1 1.1

Pcs. 1 7

Part No.

2. 3.1 3.2 3.3

1 1 1 1

PR-7310

4 5

1 1

PR-7028 PR-7311

Description Enclosure Conduit hubs 1/2” NPT-Type ST-1 (US) Divert Control Unit Card Modem transformer Modem card Modem cable Ribbon cable LED Display card

INSTRUCTION MANUAL FOR DD-01

Item 6.1 6.2

Pcs. 2 1

Part No. PR-6551 PR-6551

6.3

1

PR-6551

6.4

1

PR-6552

7.

1

PR-6501

Description Switch unit, green Switch unit, red for Emergency divert Switch unit, green for Emergency divert reset Lock unit for Automatic/Override divert operation Divert Fuse set: 9 fuses (3 x Microfuse 1A, fast IEC 1273/1, UL 198G; 3 x 5x20mm Fuse 1A, fast; 3 x Microfuse 63 mA, fast IEC 127-3/1, UL 198G) DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

36 9.2. REMOTE DIVERT CONTROL UNIT

ltem

Pcs.

Part No.

Description

6.1 6.2 6.3

2 1 1

PR-6551 PR-6551 PR-6551

6.4

1

PR-6552

8.1 8.2 8.3

1

Switch unit, green Switch unit, red for Emergency divert Switch unit, green for Emergency divert reset Lock unit for Automatic/Override divert operation PR-7310-RACK RACK-modem RACK Power 24V

1

INSTRUCTION MANUAL FOR DD-01

DOCUMENT/REVISION: IMD 1/5 Effective: June 20, 2005

Smile Life

When life gives you a hundred reasons to cry, show life that you have a thousand reasons to smile

Get in touch

© Copyright 2015 - 2024 PDFFOX.COM - All rights reserved.