Rooftop Units [PDF]

Constant volume packages rooftop units are one of the most common HVAC systems for commercial buildings. ... reer find a

162 downloads 21 Views 2MB Size

Recommend Stories


Voyager II Rooftop Units
Forget safety. Live where you fear to live. Destroy your reputation. Be notorious. Rumi

UZ Packaged Rooftop Cooling Only Units and Heat Pumps
Never wish them pain. That's not who you are. If they caused you pain, they must have pain inside. Wish

Raider® Rooftop Units 3 to 6 Tons Net Cooling Capacity
The greatest of richness is the richness of the soul. Prophet Muhammad (Peace be upon him)

Rooftop Unit
Where there is ruin, there is hope for a treasure. Rumi

Rooftop Unit
Open your mouth only if what you are going to say is more beautiful than the silience. BUDDHA

Rooftop Unit
Happiness doesn't result from what we get, but from what we give. Ben Carson

50UA-UH Packaged Rooftop Cooling Only Units, Heat Pumps and Gas Heating Units
Just as there is no loss of basic energy in the universe, so no thought or action is without its effects,

cucondensing units [PDF]
ra l Info rm ation. XX range. Features: High reliability & efficiency. New design to work under heavy duty operation conditions. Range: 16.00 to 23.00 cc. Refrigerants: R134a, R404A, R290, R407C, ...... CSIR C-V 442 618 867 11901270 623 3.56 1378 365

Course units (PDF)
No matter how you feel: Get Up, Dress Up, Show Up, and Never Give Up! Anonymous

Course units (PDF)
Stop acting so small. You are the universe in ecstatic motion. Rumi

Idea Transcript


COMMERCIAL HVAC PACKAGED EQUIPMENT

Rooftop Units

Level 1: Constant Volume

Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They are targeted at engineers and designers who wish to develop their knowledge in this field to effectively design, specify, sell or apply HVAC equipment in commercial applications. Although TDP topics have been developed as stand-alone modules, there are logical groupings of topics. The modules within each group begin at an introductory level and progress to advanced levels. The breadth of this offering allows for customization into a complete HVAC curriculum – from a complete HVAC design course at an introductory-level or to an advancedlevel design course. Advanced-level modules assume prerequisite knowledge and do not review basic concepts.

Constant volume packages rooftop units are one of the most common HVAC systems for commercial buildings. The reason for this is that these units provide cost effective, complete, preengineered air-conditioning systems with a large offering of options and accessories to adapt them to many commercial applications. In addition, the largest number of commercial buildings fall within the range covered by these units. Most HVAC designers will at sometime in their career find a rooftop unit is a good solution for a project. Even though the manufacturer fixes the selection of the internal components, the designer must have an understanding of their features, ratings, limits, options, application, and selection to properly select and apply them. This TDP module presents the basic information a designer needs to properly select and apply constant volume rooftops.

© 2006 Bryant Heating & Cooling Systems. All rights reserved. The information in this manual is offered as a general guide for the use of industry and consulting engineers in designing systems. Judgment is required for application of this information to specific installations and design applications. Bryant Heating & Cooling Systems is not responsible for any uses made of this information and assumes no responsibility for the performance or desirability of any resulting system design. The information in this publication is subject to change without notice. No part of this publication may be reproduced or transmitted in any form or by any means, electronic or mechanical, for any purpose, without the express written permission of Bryant Heating & Cooling Systems.

Printed in Syracuse, NY BRYANT HEATING & COOLING SYSTEMS PO Box 4808 Syracuse, NY 13221, U.S.A.

Table of Contents Introduction..................................................................................................................................................... 1 What is a Rooftop Unit? ................................................................................................................................. 2 Definitions and Descriptions ......................................................................................................................2 Packaged Air Conditioner (PAC)...........................................................................................................3 Year-Round Air Conditioner (YAC).....................................................................................................3 Heat Pump (HP) .....................................................................................................................................4 Discharge Air Configurations.....................................................................................................................4 Advantages and Disadvantages of Using Rooftops ....................................................................................5 Typical Rooftop Unit Markets....................................................................................................................8 Rooftop Tier Offering................................................................................................................................... 10 Rooftop Equipment Components.................................................................................................................. 11 Compressors .............................................................................................................................................11 Evaporator Coils .......................................................................................................................................12 Coil Circuiting and Expansion Devices....................................................................................................13 Condenser Coils........................................................................................................................................14 Evaporator Fans........................................................................................................................................14 Evaporator Fan Motors .............................................................................................................................16 Condenser Fans.........................................................................................................................................17 Safety Controls .........................................................................................................................................17 Rating and Efficiency Terms ........................................................................................................................ 19 Gross versus Net Capacity........................................................................................................................19 EER...........................................................................................................................................................20 SEER ........................................................................................................................................................21 IPLV .........................................................................................................................................................22 COP ..........................................................................................................................................................22 HSPF.........................................................................................................................................................23 Controlling the Rooftop Unit ........................................................................................................................ 24 Programmable Thermostat........................................................................................................................24 Direct Digital Control ...............................................................................................................................25 DDC Networks .........................................................................................................................................26 Sequence of Operation..............................................................................................................................27 Codes and Standards..................................................................................................................................... 28 UL/ETL/CSA............................................................................................................................................28 ARI ...........................................................................................................................................................28 ASHRAE ..................................................................................................................................................28 Indoor Air Quality and Sustainable Design (LEEDTM) ............................................................................30 Application Topics........................................................................................................................................ 31 Normal Rooftop Unit Operating Conditions.............................................................................................31 Refrigerants ..............................................................................................................................................32 Controlling Room Humidity.....................................................................................................................33 Supply Air Reheat Dehumidification Options ..........................................................................................34 Reheat and ASHRAE 90.1 Impact .......................................................................................................36 Pretreating Outside Ventilation Air ..........................................................................................................36 Air-to-Air Energy Recovery.................................................................................................................37 Dehumidification Combined with an Energy Recovery Device ..........................................................37 Demand Controlled Ventilation for IAQ ..................................................................................................38 Heat Pump versus Gas versus Electric Heat .............................................................................................41 Minimum Entering Temperatures to Gas Heat Exchanger .......................................................................42 Additional Placement Considerations for Rooftop Products ....................................................................42 Clearances ............................................................................................................................................43 Visual Considerations ..........................................................................................................................44 Support for the Unit..............................................................................................................................45 Sound Considerations...........................................................................................................................45 Installation Considerations for Gas Heat Rooftop Units ..........................................................................45

Electrical Data .............................................................................................................................................. 46 Minimum Circuit Amps (MCA)............................................................................................................... 46 Maximum Over-Current Protection (MOCP)........................................................................................... 47 Recommended Overcurrent Protection (ROCP)....................................................................................... 47 Disconnects .............................................................................................................................................. 47 Sizing the Disconnect:.......................................................................................................................... 48 Location of Disconnects....................................................................................................................... 48 Types of Overcurrent Protection .......................................................................................................... 49 Single-Point Power................................................................................................................................... 49 Replacement Rooftop Considerations........................................................................................................... 50 Options and Accessories............................................................................................................................... 53 Economizers ............................................................................................................................................. 53 When to Use an Economizer................................................................................................................ 54 Economizer Control Methods .............................................................................................................. 54 A, B, C, and D Scale Economizer Settings .......................................................................................... 56 Manual Outdoor Air Damper ............................................................................................................... 57 Motorized Two-Position Outdoor Air Damper .................................................................................... 57 Barometric Relief Dampers ...................................................................................................................... 58 Powered Exhaust ...................................................................................................................................... 58 Smoke Control.......................................................................................................................................... 59 Corrosion-Resistant Coil Options............................................................................................................. 60 Standard Coil Construction .................................................................................................................. 60 Pre-Coated Aluminum-Fin Coils ......................................................................................................... 61 Copper-Fin Coils.................................................................................................................................. 61 Electro-Coated Coils ............................................................................................................................ 61 Coil Guards............................................................................................................................................... 62 Hail Guards............................................................................................................................................... 62 Low Ambient Cooling Operation ............................................................................................................. 63 Heating Options........................................................................................................................................ 64 Gas ....................................................................................................................................................... 64 LP Gas Versus Natural Gas.................................................................................................................. 65 Altitude Adjustment – Gas Heating ..................................................................................................... 65 Gas Emission Restrictions (Low NOx)................................................................................................. 66 Electric Heat......................................................................................................................................... 66 Hot Gas Bypass ........................................................................................................................................ 67 Field-Installed VFD for Constant Volume Rooftop Unit ......................................................................... 68 Convenience Outlets................................................................................................................................. 68 Roof Curbs ............................................................................................................................................... 69 Roof Curb Types .................................................................................................................................. 69 Roof Curb Alignment........................................................................................................................... 72 Roof Curb Installation.......................................................................................................................... 72 Adapter Roof Curb Installation ............................................................................................................ 73 Roof Curb and Electric Heat Requirements ......................................................................................... 74 Thru-the-Curb Utilities......................................................................................................................... 74 Rooftop Unit Sound...................................................................................................................................... 75 Sound Mitigation Suggestions.................................................................................................................. 76 Existing Installations............................................................................................................................ 76 Pressure Dependent Zoning System ............................................................................................................. 77 Selecting Rooftop Equipment....................................................................................................................... 78 Standard ARI Rating Conditions .............................................................................................................. 78 Typical Rooftop Unit Published Ratings .................................................................................................. 79 Rooftop Unit Selection Example: Gas Heating (YAC) ............................................................................ 79 Summary....................................................................................................................................................... 85 Work Session................................................................................................................................................ 86 Appendix ...................................................................................................................................................... 88 References ................................................................................................................................................ 88 Work Session Answers............................................................................................................................. 89

ROOFTOP UNITS, LEVEL 1: CONSTANT VOLUME

Introduction Packaged constant volume rooftop units are one of the largest and most important segments of the air-conditioning industry, primarily due to their all-inclusive design, low cost, application flexibility, ease of installation, and widespread use. This TDP module will give you an understanding of the types of constant volume rooftops, their application, available options and accessories, and guidelines for their use and installation. The function of commercial packaged rooftop equipment is to provide complete air conditioning, including control of temperature, humidity, air circulation, exhaust, energy recovery, and filtration. Although standard rooftop units do not directly control relative humidity in most cases, they dehumidify the air, which usually results in acceptable humidity levels. While all rooftop units provide mechanical cooling, some are equipped with a gas-heating system while oth- Figure 1 ers use electric heaters, steam or hot 2-25 Ton Constant Volume Rooftop Units water coils to provide year-round control of temperature. Packaged rooftop units are generally available in sizes from 1½ tons to over 100 tons of cooling capacity. Two types of airflow control are available within this tonnage are the largest segment of products called packaged range: constant volume, in which the volume of air is conequipment, and account for stant and the air temperature is modulated to match cooling almost one-half of the total load requirements, an variable volume, in which the temcommercial unitary market. The perature is constant and the volume of air is modulated. complete air conditioner is While much of the construction of these two unit types is contained in one package, the same, there are several special construction features ranging in size from 1.5 to over necessary in variable volume units. Generally, units under 105 tons cooling capacity. 20 tons tend to be constant volume type and units over 30 tons tend to be variable volume. However, much smaller units are available as variable volume and units to over 100 tons are used in constant volume applications. This TDP module covers primarily 2 to 25 ton constant volume (CV) commercial rooftop air conditioners. Units five ton and smaller are sometimes used for residential applications due to the special requirements of residential units, this application is not covered in this TDP. Much of the material in this module can be applied to larger tonnage constant volume units as well. Packaged rooftop units

Commercial HVAC Equipment

1

ROOFTOP UNITS, LEVEL 1: CONSTANT VOLUME

What is a Rooftop Unit? The term “packaged” is defined as products that fall within the unitary air conditioner category as defined by the Air Conditioning and Refrigeration Institute (ARI). ARI states that a unitary air conditioner consists of one or more factory-made assemblies that normally include: an evaporator or cooling coil, evaporator fan, compressor, and condenser combination. (It may include a heating function as well.) When these components are integrated into one cabinet, they are single packaged units. When provided in separate assemblies and designed to be used together, they are split systems. Since these units are most often placed on the roof, single package units are commonly called “rooftop” units. However, they also can be slab-mounted on the ground. They are usually available with either vertical or horizontal supply and return air connections. On a typical rooftop unit, the compressor(s) c are located at one end and the condenser coils d are wrapped around or in close proximity to them. Filters e are positioned on the entering airside of the evaporator coil. These are typically one or two-inch throw-away filters. Figure 2 shows a gas-fired rooftop unit so the flue gas exhaust fan and its discharge f are shown. The unit controls are located in an electrical compartment g. The gas heat exchanger h is located in a separate section on the downstream side of the evaporator fan. A perimeter base rail assembly i is used to support the unit when placed on its curb (not shown) and to handle and rig the unit. The evaporator coil j is two, three, or four rows deep and is a draw-thru design in front of the indoor fan k which discharges air into the heater then down the supply duct. Direct-drive propeller fans l draw outside air across the Figure 2 condenser coils and discharge the Components of a Typical Rooftop warmed air upwards. Rooftop units are designed, tested and certified with national safety certification agencies such as Underwriter’s Laboratories (UL), Electrical Testing Laboratories (ETL), and Canadian Safety Agency (CSA.).

Definitions and Descriptions ARI categorizes packaged rooftop units by the ability to provide heating. These categories are single packaged air conditioner (SP-A), single packaged year-round air conditioner (SPY-A), and single packaged heat pump (HSP-A). In this text we will use three commonly accepted acronyms for these units. SP-A will be referred to as PAC, SPY-A as YAC (with gas heat), and HSP-A as HP.

Commercial HVAC Equipment

2

ROOFTOP UNITS, LEVEL 1: CONSTANT VOLUME

Packaged Air Conditioner (PAC) A PAC is a packaged air conditioner (rooftop unit) that provides cooling only, or cooling with other than gas heat. The primary function of the PAC is cooling. Electric heaters are typically available factory installed as an accessory for field installation. Sometimes, PACs are called “all electric” or “electric-electric” because the source of heat is usually an electric resistance coil. Steam or hot water coils are offered as accessories by some manufacturers, and the rooftop unit is still referred to as a PAC. That is because the PAC unit does not have gas heat.

Figure 3 Packaged Air Conditioner (PAC) No Gas Heat

Year-Round Air Conditioner (YAC) A YAC is a packaged unit with a gas heating section. It is called year-round because heating and cooling are integral factory-installed unit functions. Gas heating sections are normally designed for natural gas, but propane models or propane conversion kits are typically available. Note: A YAC is also known as a gas-electric unit.

Figure 4 Rooftop – Year Round Air Conditioner (YAC) Contains Gas Heat

Commercial HVAC Equipment

3

ROOFTOP UNITS, LEVEL 1: CONSTANT VOLUME

Heat Pump (HP) A heat pump rooftop unit looks just like a PAC from the outside but the mechanical refrigeration cycle inside is different. The refrigeration cycle provides both cooling and reverse cycle heating. In the heating mode, the refrigerant flow is reversed using a four-way valve so that heat is extracted from the outdoor air and transferred to the indoor air. The heat pump is not just a PAC with a fourway valve, however. The evaporator and condenser are larger and the metering device arrangement is different to allow for the dual role. Because the heat pump does not heat efficiently at very low outdoor temperatures and to provide heating during defrost, the Figure 5 unit often contains optional electric Heat Pump Refrigeration Cycle in Rooftop Unit – Cooling Mode heaters that supplement the reverse cycle heat.

Discharge Air Configurations Shown is a vertical, or down supply air discharge as well as a vertical return configuration. Next to it is a horizontal discharge and return configuration. If the unit features both vertical supply and return and horizontal supply and return it is referred to as a “convertible” design. For vertical discharge the ductwork that delivers the conditioned airflow from the rooftop unit to the space and returns the air back to the rooftop should be attached to the curb and NOT the rooftop. The unit is simply placed on top of the curb using a crane or helicopter. The curb is a sheet metal platform that supports the unit.

Figure 6 Rooftop Discharge Air Configurations

Many rooftop designs offer horizontal supply and return duct connections in addition to vertical. Many of these designs are installed on grade (ground level) on a concrete slab.

Commercial HVAC Equipment

4