What is bulk modulus - Investor Relations Solutions [PDF]

bulk modulus to 55% of its room temperature value. If these two conditions occur simultaneously, the net effect is to re

0 downloads 7 Views 730KB Size

Recommend Stories


Sustainability Report - Investor Relations Solutions [PDF]
[SO3] In September 2013, Endesa. Chile incorporated the IT platform. “CampusLatam” a low modality e-learning course on the Criminal Risk. Prevention Model (MPRP, Modelo de. Prevención de Riesgos Penales), which includes topics relative to the Et

Investor Relations
Don't watch the clock, do what it does. Keep Going. Sam Levenson

Investor Relations
You have survived, EVERY SINGLE bad day so far. Anonymous

Rheinmetall AG – Investor Relations
Learn to light a candle in the darkest moments of someone’s life. Be the light that helps others see; i

Investor Relations Report
Learning never exhausts the mind. Leonardo da Vinci

Untitled - Dropbox Investor Relations
The beauty of a living thing is not the atoms that go into it, but the way those atoms are put together.

Investor relations policy
The best time to plant a tree was 20 years ago. The second best time is now. Chinese Proverb

The investor relations officer
Ego says, "Once everything falls into place, I'll feel peace." Spirit says "Find your peace, and then

Investor Relations Presentation
Happiness doesn't result from what we get, but from what we give. Ben Carson

investor relations policy
Do not seek to follow in the footsteps of the wise. Seek what they sought. Matsuo Basho

Idea Transcript


SYSTEM DESIGN By Herman F. George and Allan Barber The Lubrizol Corp., Wickliffe, Ohio

What is bulk modulus, and when is it Important?

D

You should consider bulk modulus of a hydraulic fluid if position, response time, and stability are critical.

0707HP34-39.indd 34

espite the frequent assumption that hydraulic fluid is incompressible, the fact remains: All fluids have some degree of compressibility. Granted, fluid compressibility may be neglected in systems that do not require tight control of response and where operating pressure and fluid volume are moderate. However, when applying high pressure to a large volume of fluid, a significant amount of energy can be expended to compress the fluid — essentially squeezing the fluid’s molecules closer together. The result can be delayed response — a loaded actuator may not move until upstream fluid has been compressed, and the energy stored in the fluid may cause the actuator to continue moving after its control valve has closed. Bulk modulus is a property that indicates the compressibility of a fluid. With many of today’s hydraulic systems operating at pressures 5000 psi and higher, ignoring bulk modulus can compromise response time of a system. Applied pressure should directly affect the action of the system rather than compress the fluid.

8/7/07 3:34:28 PM

SYSTEM DESIGN

Compressing fluid wastes power

P2

P1

V2

V1 Volume — m3

V0

Figure 1. Increasing the pressure applied to a fluid decreases its volume.

What is bulk modulus? Most substances diminish in volume when exposed to a uniform, externally applied pressure. A typical plot of volume, V, versus pressure is shown in Figure 1. The curve shows that volume of the fluid, V, is a function of applied pressure, P, compressibility of the fluid, k, and initial volume of the fluid, V0: V = f (P, V0, k) V0 = initial volume, in3, l, or m3 P = pressure, psig, Pa, or bar k = compressibility, usually negative, in.2/lb (V-V0) ÷ V = specific volume, commonly used for x-axis The term bulk modulus usually

10 9

Bulk modulus 50,000 psi 100,000 psi 200,000 psi 300,000 psi

8 7 6 5 4 3 2 1 0 0.1

0.5

0707HP34-39.indd 36

2.0

The larger the size, the greater the effect 35 Bulk modulus 50,000 psi 100,000 psi 200,000 psi 300,000 psi

30 25 20

Figure 3. Power lost at 3000 psig for 1 in.2 of piston area and 10-in. stroke during short time intervals for various bulk moduli.

15 10 5 0 0.01

0.02 Time — sec

Pa, N/m2). Thus, the bulk modulus is a measure of resistance to compressibility of a fluid. A flat slope signifies a fairly compressible fluid having a low bu l k m o d u lus. A steep slope indicates a stiff, or only slightly compressible fluid.

“Bulk modulus is a measure of a fluid’s resistance to compressibility.” means the reciprocal of compressibility and defines the slope of the curve when plotted against specific volume, Figure 1. Because specific volume is dimensionless, units of bulk modulus are the same as pressure — psig (bar,

1.0 Time — sec

Figure 2. Power lost at 3000 psig for 1 in.3 of cylinder volume over time for various bulk moduli.

Power loss — hp/in.2 of piston area

This is why it is so important to design systems with as little fluid as possible beween the control valve and the actuator.

Power loss — hp/in.3 of cylinder volume

Pressure — Pa

The pressure is on volume

Defining bulk modulus The plot in Figure 1 is not a straight line, so its slope changes from point to point. Two common methods are used to define the slope, or bulk modulus1: Secant bulk modulus is the product

0.03

0.04

of the original fluid volume and the slope of the line drawn from the origin to any specified point on the plot of pressure versus specific volume (the slope of the secant line to the point). Mathematically, secant bulk modulus, BS, is: BS = (V0 × P) ÷ (V0 –V) Tangent bulk modulus is the product of fluid volume at any specified pressure and the derivative of fluid pressure with respect to volume at that point (the slope of the tangent line to the point). Mathematically, tangent bulk modulus, BT, is: BT = V0 (dP/dV) Before giving some typical values for bulk moduli, we must take one

8/7/07 3:37:56 PM

SYSTEM DESIGN

Fluid type

Isentropic secant bulk modulus at 20° C and 10,000 psi

Water – glycol

500,000 psi

Water-in-oil emulsion

333,000 psi

Phosphate ester

440,000 psi

ISO 32 mineral oil

260,000 psi

Power loss relationships Minimum power at 100 Hz — hp

30

B = 50,000

24 Hp = 1.75 Q 18

B = 100,000

12 B = 300,000 6 0 5

10 Flow — gpm

15

20

Table 1. Values of isentropic secant modulus for typical hydraulic fluids at a fixed pressure and temperature.

Figure 4. Power loss to total system power available.

more variable into consideration, namely, temperature. Temperature and bulk modulus Temperature is important because as fluid compresses its temperature rises. As the temperature rises, the fluid attempts to expand, which, in turn, creates additional pressure. This can occur rapidly or slowly. Compressing the fluid very slowly allows generated heat to dissipate. This bulk modulus is called isothermal (constant temperature) bulk modulus. Adiabatic or isentropic bulk modulus occurs by compressing the fluid rapidly and measuring the pressure — even though it results from both compression and thermal expansion. Because we are concerned with rapidly moving, tightly controlled systems, most hydraulic applications are considered isentropic. Therefore, most of the bulk moduli discussed here are isentropic. Table 1 shows values of isentropic secant modulus for some typical hydraulic fluids at a fixed pressure and temperature. Effect of air on bulk modulus Designers should be cautious before using published bulk modulus values. The values usually are determined by

0707HP34-39.indd 38

% of air

Temperature, Isentropic bulk °F modulus, psi

laboratory methods that take spe0.0 80 268,000 cial precautions to degas the fluid 0.1 80 250,000 before it is trapped 1.0 80 149,000 and compressed. However, hydrau0.0 180 163,000 lic fluids typically become aerated in 1.0 180 106,000 use. Aeration has a significant effect Table 2. Raising the temperature of commercial hydraulic fluid on bulk modulus by 100° F alone reduces its bulk modulus to 61% of its roombecause air is much temperature value. Introducing 1% air by volume reduces the more compressible bulk modulus to 55% of its room temperature value. If these two than oil. George conditions occur simultaneously, the net effect is to reduce the Totten 2 discusses bulk modulus by 67%. estimating the effects of air in oil on compressibility the bulk modulus of the fluid. In and bulk modulus. Also, realize that the case of pumps, the percentage the solubility of air in fluids increases volume loss in the output is seen as with pressure. Air dissolved in a fluid a loss of horsepower. For masterat high pressure can form bubbles slave cylinders, the volume loss is when pressure drops — a phenomenon seen as a reduced stroke from the that can cause cavitation. slave. Stopping a moving load — If a cylPredicting bulk modulus inder moves a load at a uniform velocSeveral sources are available for ity (that is, constant flow to the cylinpredicting the bulk modulus of hy- der), the cylinder has momentum that draulic fluids2,3. the fluid and the system must absorb Volume lost in pumps and ac- when a valve controlling upstream and tuators — The output of a pump or downstream flow is suddenly closed. the positional relationship of mas- The downstream fluid pressure will ter and slave cylinders varies with rise from some nominal value to some

8/7/07 3:38:14 PM

peak pressure as energy is absorbed. Assuming the cylinder and hydraulic lines to be rigid, and a linear rise in pressure, the fluid’s bulk modulus will determine peak pressure. Thus, for a specific maximum pressure, the stiffer the fluid, the less energy is absorbed and the less overshoot. Fluids with higher values of bulk modulus have less energy absorption and less piston overshoot, which translates to better position accuracy. Fast load reversals — Because most fluids are compressible, the fluid in an actuator must be compressed before the cylinder or piston will move a load. In other words, an amount of fluid equal to the compressed volume must be added to an actuator before a load will move. Because this pro-

der volume for various bulk moduli, Figure 2. Lost power increases as cylinder size increases and response time decreases. Figure 3 illustrates lost power versus response rate for various bulk moduli. The loss in power may look relatively small until we consider an average cylinder. If we assume a bulk modulus of 200,000 psi, a response of 100 Hz, and a stroke of 10 in., the power loss is 6.75 hp / in.2 of ram area. Figure 4 relates power loss to total system power available. For example, a 3000-psi, 3.8-gpm system that can supply 6.75 hp cannot move a load at 100 Hz with a 1-in.2 piston because all the power is used in compressing the fluid.

“Aeration has a significant effect on bulk modulus because air is much more compressible than oil.” cess does not do useful work, it is lost work: WL = f × d where WL = lost work f = force d = distance Distance refers to an increment of cylinder stroke, so: WL = ∆P × ∆V0 where ∆P = change in pressure ∆V = change in volume (increment of stroke × piston area) But ∆V = ∆P × (V0 ÷ B), so: WL = (∆P2 × V0 ) ÷ B To calculate lost power, divide by time: WL = (∆P2 × V0) ÷ (Bt × 6600) Because power loss can be significant at higher pressure ranges, let us examine a typical 3000 psig system, that is, ∆P = 3000 psi. hpl = (1363 V0) ÷ (B × t) It is now possible to plot lost horsepower versus time for 1 in.3 of cylin-

Resonance of hydraulic systems The natural frequency of a springmass combination is: ƒ = (1 ÷ 2π) × (kg)1/2 ÷ W Where: ƒ = frequency, Hz W = weight, lb k = spring rate, lb/in., and g = acceleration due to gravity, 32.2 ft/sec2. To equate this to a hydraulic system, we only need to substitute bulk modulus for spring rate. Thus, a low modulus also lowers the natural frequency of a system. For example, if 1% air content changes the bulk modulus by 50%, its natural frequency decreases by 30%. This greatly reduces the stability of the system. Why bulk modulus is important We can conclude, then, that the absolute value of the bulk modulus of a fluid can seriously affect system

performance in relation to position, power level, response time, and stability. Two factors that figure prominently in the control of bulk modulus are fluid temperature and entrained air content. For example, Table 2 shows that raising the temperature of commercial hydraulic fluid by 100° F alone reduces its bulk modulus to 61% of its room-temperature value. Table 2 also indicates that introducing 1% air by volume reduces the bulk modulus to 55% of its room temperature value. If these two conditions occur simultaneously, the net effect is to reduce the bulk modulus by 67%. In view of today’s requirements for higher power and response time, it is more important than ever to pay attention to bulk modulus. References: 1. ASTM D6793 “Standard Test Method for Determination of Isothermal Secant and Tangent Bulk Modulus,” ASTM International, West Conshohocken, Pa. 2. Handbook of Hydraulic Fluid Technology, edited by George E. Totten, Marcel Dekker, Inc., 2000. 3. Hydraulic Fluid Power — Petroleum Fluids — Prediction of Bulk Moduli, ANSI.NFPA T2.13.7 R1-1997 (R2005) National Fluid Power Association, Milwaukee.

The Lubrizol Corporation 29400 Lakeland Blvd. Wickliffe, Ohio 44092 www.lubrizol.com

Copyright © 2007 by Penton Media, Inc.

0707HP34-39.indd 39

8/7/07 3:38:37 PM

Smile Life

When life gives you a hundred reasons to cry, show life that you have a thousand reasons to smile

Get in touch

© Copyright 2015 - 2024 PDFFOX.COM - All rights reserved.